Multi IR Flame Detector 3600-M
he 3600-M uses infrared (IR) technology, a reliable design that provides early warning of flaming fires and immunity to false alarms from IR sources such as sunlight and IR projectors.
The 3600-M utilizes a Multi-Spectrum Design, allowing it to detect hydrocarbon and hydrogen flames up to 215 feet away. It can detect a gasoline pan fire at 215 feet or a hydrogen flame at 100 feet in less than 5 seconds. Users can also select different sensitivity levels to ensure no other detectors cross-over detection zones. Other features include a heated window to eliminate condensation and icing, HART and Modbus capabilities for digital communications, low power requirements, and a compact design.
The Multi IR Flame Detector 3600-M is approved and certified by a variety of third party agencies, including FM, ATEX, IECEx, TUV, and CSA. These approvals and certifications assure our customers that we carry only the highest quality of products and performance.
1. MULTI-SPECTRUM DESIGN
Detect hydrocarbon and hydrogen flames up to 215 feet away
2. IR SENSITIVITY SELECTION
Choose between short and long distance sensitivity ranges, depending on the needs and function
3. 5-SECOND RESPONSE
Quickly respond and alarm users of a fire in a swift manner
4. HEATED WINDOW
Eliminate any possible condensation or icing to ensure the detector to function properly
5. LOW POWER REQUIREMENTS
Save energy costs while protecting the facility
6. MULTIPLE OUTPUT OPTIONS (RELAY OUTPUTS, 0-20 MA, HART, MODBUS RS-485)
Easily install in a variety of field applications and easily obtain critical safety information wherever needed with maximum flexibility and compatibility
Model Number | 3600-M | ||||||||||||||||||||||||||
Spectral Response | Multi IR Bands | ||||||||||||||||||||||||||
Detection Range | (At highest Sensitivity Setting for 1 sq. ft. / 0.1 sq. m pan fire)
*20” (0.5 m) high, 8” (0.2 m) with plume fire | ||||||||||||||||||||||||||
Response Time | Typically 5 seconds | ||||||||||||||||||||||||||
Adjustable Time Delay | Up to 30 seconds | ||||||||||||||||||||||||||
Sensitive Range | 4 Sensitive Ranges for 1 sq. ft. (0.1 sq. m) n-heptane pan fire from 50 ft. (15 m) to 215 ft. (65 m) | ||||||||||||||||||||||||||
Field of View | Gasoline: 67o horizontal, 70o vertical Hydrogen: 80o horizontal, 80o vertical | ||||||||||||||||||||||||||
Built-in-Test (BIT) | Manual and Automatic | ||||||||||||||||||||||||||
Temperature Range | Operating: -67oF to 167oF (-55oC to 75oC) Operating Option: -67oF to 185oF (-55oC to 85oC) Storage: -67oF to 187oF (-55oC to 85oC) | ||||||||||||||||||||||||||
Humidity | Up to 95% non-condensing (withstands up to 100% RH for short periods) | ||||||||||||||||||||||||||
Heated Options | To eliminate condensation and icing on the window | ||||||||||||||||||||||||||
Electrical Specifications | Operating Voltage: 24 VDC nominal (18-32 VDC) Power Consumption:
Cable Entries: 2 x ¾” – 14 NPT conduits or 2 x M25 x 1.5 mm ISO Wiring: 12 – 22 AWG (2.5 mm 2 – 0.3mm2) Electrical Input Protection: According to MIL-STD-1275B Electromagnetic Compatibility: EMI/RFI protected to EN61326-3 and EN61000-6-3 Electrical Interface: The detector includes twelve (12) terminals with five (5) wiring options (factory set) | ||||||||||||||||||||||||||
Outputs | Relays:
4-20 mA (stepped)
HART Protocol: Optional HART communication on the 0-20 mA analog current (FSK) – used for maintenance, configuration changes and asset management, available in mA source output wiring options RS-485: RS-485 Modbus compatible communication link that can be used in computer control installations | ||||||||||||||||||||||||||
Mechanical Specifications | Materials/Enclosure Options: Heavy-duty copper free aluminum (less than 1%), red epoxy enamel finish (ATEX Approval only) Stainless Steel 316L with electro polish finish (FM or ATEX Approval) Mounting: Stainless Steel 316L with electro polish finish Dimensions:
Weight
Environmental Standards: Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock , High Temp, Low Temp Water and Dust: IP66 and IP67 per En60529, NEMA 250 6P | ||||||||||||||||||||||||||
Approvals | Hazardous Area
Performance
Reliability
| ||||||||||||||||||||||||||
Accessories | Fire Simulator: 20/20-310 Tilt Mount: 3600-01 Weather Protector: 777163 Air Shield: 777650 Mini Laptop Kit: 777820 USB RS-485 Harness Kit: 794079-5 Laser Pointer (Detector Area Coverage): 777166 |