Responsive Menu
Add more content here...
Ateva Technologies

mbGate PB

Passerelle : Réseaux Modbus TCP vers des réseaux PROFIBUS PA/DP

Avec la passerelle mbGate PB, nous pouvons désormais intégrer jusqu’à 2 segments PROFIBUS PA et 1 segment PROFIBUS DP à un système de controle Modbus TCP. La passerelle agit comme un serveur Modbus TCP  et un maitre PROFIBUS. Avec cette gateway, le cout de l’intégration est considérablement réduit.  Elle permet la paramétrisation et l’utilisation des outils standard de management.

Key Component for Transition to State-of-the-Art Technology

  • Simple replacement of installed PROFIBUS DP/PA segment couplers
  • Re-use of existing PROFIBUS segments without requiring modification

Direct Connectivity to PROFIBUS Segments

  • Single access point to PROFIBUS DP and PROFIBUS PA segments from Modbus TCP networks
  • Acting as Modbus TCP Server and PROFIBUS PA and PROFIBUS DP Master
  • Support of one PROFIBUS DP segment and up to two PROFIBUS PA segments

Configuration, Parameterization and Plant Asset Management Using Standard Industry Tools

  • Supports major Modbus engineering tools such as Schneider Unity Pro or Siemens TIA Portal
  • Included CommDTM allowing use in FDT/DTM frame applications
  • EDD-based device parametrization using Siemens Simatic PDM

MODBUS/TCP Redundancy

  • Supports the use of two redundant PLCs and two redundant gateways
  • Easily enabled via licensing
  • Full control of redundant operation mode via engineering and PLC
Scope of Delivery
HardwarembGate PB Gateway
DocumentationOn Website
Order Numbers
GCA-EN-024808mbGate PB, Modbus TCP to PROFIBUS Gateway. Supports 2 PA segments (up to 32 PA devices, MBP physical layer) and 1 PROFIBUS DP segment (RS485).
Additional Products and Services
LRA-EN-024851gatePlus HighAvailability, License for activating redundancy features in mbGate PB
LRL-DY-134501dataFEED OPC Suite, Version 4.01 and higher, including all supported PLC protocols, support for OPC UA, access for any number of dataFEED OPC Tunnel Clients, for simultaneous access to a total of up to 100 OPC UA Servers, OPC Servers and OPC Tunnel Servers, and many more Functionalities such as Database and File Access, Data Exchange, Optimizer, Concentrator and Bridge
GCA-EL-024802mbGate PA, Modbus TCP to PROFIBUS PA Gateway. Supports up to 2 PA segments (up to 32 PA devices).
GCA-EL-024804mbGate PA, Modbus TCP to PROFIBUS PA Gateway. Supports up to 4 PA segments (up to 64 PA devices).
GCA-EN-024806mbGate DP, Modbus TCP to PROFIBUS DP Gateway. Supports 1 PROFIBUS DP segment (RS485).

Video Channel : Retrouvez nous sur notre page channel YOUTUBE 

pnGate PA

Passerelle PROFINET vers PROFIBUS PA (pnGate PA)

Intégration de segments PROFIBUS PA dans un sytème de contrôle PROFINET

  • Ré-utilsez vos power Conditioner dans une technologie plus avancée ?
  • Pas de segments PROFIBUS DP intermédiaires.
  • Préparé pour une intégration standard et pour les outils d’administration

Passerelle PROFINET : La clef essentiel pour une transition vers des technologies de pointe.

  • Passerelle PROFINET : Simple replacement des coupleurs PROFIBUS PA/DP
  • Ré-utilsation des segments PROFIBUS PA sans aucune modification
  • Support de la redondance PROFINET, afin d’accroitre la fiabilité.

Connexion directe aux segments PROFIBUS

  • Cette passerelle PROFINET/PROFIBUS PA est assimilé à un device PROFINET et un maître PROFIBUS PA
  • Supporte jusqu’à 4 segments PROFIBUS PA

Configuration, paramétrisation et outils d’administration aux Standard en vigeur pour cette passerelle PROFINET / PROFIBUS PA

  • Supporte  les outils PROFINET tels que: TIA Portal, Step7 et PC WORXS
  • Incluant  CommDTM et permettant l’utilisation d’applications FDT/DTM
  • Parametrisation EDD possible via Simantic PDM
Technical Details
HardwareProcessor
Status LEDs (Gateway)Status LEDs (Fieldbus)
Altera Cyclone V SoC with dual-core ARM Cortex-A9
PWR (power supply), RUN (operation), ERR (error), CFG (configuration and update)
SF (system fault), BF (bus fault)
Interfaces and ConnectorsEthernet

PROFIBUS PA

2 * IEEE 802.3 100BASE-TX / 10BASE-T, embedded PROFINET switch for daisy chain topology
Connectors: RJ45
Protocol: PROFINET RT / IRT, Support of PROFINET redundancy protocols
RESTful API interface for device configuration
Up to 4 PROFIBUS PA (MBP) segments (refer to the section “Order Numbers”),
Bus-powered Medium Attachment Unit (MAU): Fieldbus voltage range: 9 VDC … 32 VDC,
current consumption 10 mA,
Connectors: 3-position screw connection, galvanically isolated
Physical PropertiesDimensions (H x W x D)
Weight
Power SupplyOperating / Storage Temperature
Relative Humidity
Cooling
Coating
Mounting
Protection Class
100 mm x 35 mm x 105 mm
About 0.25 kg
18 VDC … 32 VDC; SELV/PELV power supply mandatory
Typical input current: 200 mA, maximum input current: 1 A (allowing for in-rush current at switch-on)
No power supply to PROFIBUS PA segments through pnGate PA
-40 °C … +70 °C / -40 °C … +85 °C
(see detailed mounting description in user manual)
10 % … 95 %, non-condensing
Convection, no fan
Conformal coating based on ANSI / ISA-S71.04 G3
DIN rail 35 mm
IP20
Scope of Delivery
HardwarepnGate PA Gateway
SoftwareGSDtoGSDML Converter, FDT CommDTM, PACTware, Drivers and Tools
DocumentationOn CD-ROM
Order Numbers
GCA-AL-024602pnGate PA, PROFINET to PROFIBUS-PA Gateway. Supports up to 2 PROFIBUS PAsegments (up to 32 PA devices).
GCA-AL-024604pnGate PA, PROFINET to PROFIBUS-PA Gateway. Supports up to 4 PROFIBUS PAsegments (up to 64 PA devices).
GCA-AL-024605pnGate PA (for STAHL carrier), PROFINET to PROFIBUS-PA Gateway. Supports up to 4 PROFIBUS PA segments (up to 64 PA devices). For reversed mounting position on STAHL backplane.
Additional Products and Services
GCA-EL-024802mbGate PA, Modbus/TCP to PROFIBUS-PA Gateway. Supports up to 2 PROFIBUS PA segments (up to 32 PA devices).
GCA-EL-024804mbGate PA, Modbus/TCP to PROFIBUS-PA Gateway. Supports up to 4 PROFIBUS PA segments (up to 64 PA devices).

Si vous avez besoin de Firmware antérieur, veuillez nous contacter :  support@fr.atevatech.com

Les personnes intéressés par ce produit, peuvent aussi être intéressés par : 

  • pnGate PB : PROFINET to PROFIBUS Gateway. Supports up to 2 PROFIBUS PAsegments (up to 32 PA devices, MBP physical layer) and 1 PROFIBUS DP segment (RS485).

dataFEED uaGate MB

dataFEED uaGate Modbus TCP

Passerelle pour OPC UA et communication MQTT vers PLCs Modbus TCP

  • Fonctionalité de communication OPC UA
  • Import des symboles utilisant les données du contrôleur via interface web ?
  • Haute protection assurée pour le transfert des données

Accès des données Modbus de votre PLC pour les applications OPC UA

  • Accès aux contrôleurs Modbus, ex:.  Schneider Electric, Wago, Beckhoff, Phoenix Contact, etc….
  • Intégration complète dans les systèmes de “Managements” comme : ERP, MES ou SCADA utilisant un serveur OPC UA, fournissant une plateforme indépendante fiable et sécurisée.
  • Accès aux données locales et globales facile et intégration facile et rapide à travers les pare-feux
  • Spécialement conçu pour des mises à jours de systèmes vieillissant et limitant ainsi, les investissements lourds.
  • Pas besoin de mise à jours logiciel, opérating systems, ce qui limite les risques de “crash” à long terme.
  • Programmation PLC minimale pour la configuration des registres
  • Pas besoin de PC dédié

Données de projets PLC disponibles pour utilisation spécifique

  • Import des symboles depuis fichier TXT
  • Installation simple et facile du serveur OPC, qui ne demande que quelques étapes pour l’accès des données PLC Modbus
  • Interface “Web-based” pour la configuration

Sécurité de type industriel “maximale”

  • Séparation physique des interfaces et séparations des droits pour les réseaux OT et IT.
  • Supportant les standards de sécurité tel que : SSL/TLS et certificats X.509
  • Encryption des données au standard OPC UA et authentification des utilisateurs
  • Securité supportée pour la communication MQTT avec cléf privée et ” clouds ” publics
HardwareProcessorAltera Cyclone V SoC with Dual-core ARM Cortex-A9
Connectors2 x IEEE 802.3 100BASE-TX/10BASE-T (independent interfaces)
Status LEDsPWR (power supply), RUN (running), ERR (error), SYS (configuration)
Dimensions (H x W x D)100 mm x 22.5 mm x 105 mm
Power Supply18 VDC … 32 VDC, SELV/PELV supply mandatory Typically 200 mA, maximum 1 A at switch-on
Operating Temperature, Horizontal DIN Rail Installation-40 °C .. 50 °C (0 mm minimum distance)
-40 °C .. 55 °C (22.5 mm minimum distance)
Operating Temperature, Vertical DIN Rail Installation-40 °C .. 35 °C (0 mm minimum distance)
-40 °C .. 40 °C (22.5 mm minimum distance)
Storage Temperature-40 °C .. 85 °C
Relative Humidity10 % … 90 %, non-condensing
WeightAbout 0.2 kg
MountingDIN Rail (35 mm)
HousingPhoenix Contact ME MAX
Protection ClassIP20
SoftwareProtocolsModbus TCP, OPC UA (Server, 20,000 items in total), MQTT (Publisher, up to 1,000 topics)
Supported ControllersModbus TCP controllers, e.g. from Schneider Electric, Wago, Beckhoff, Phoenix Contact, etc.
ConformityEmissionEC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55011, Group 1, Class A
EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55022, Class A
EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-4
FCC CFR45, Part 15 Section 15.107 and 15.109 (Class A),
VCCI Class A Information Technology Equipment 2002
ImmunityEC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-2
ATV-GAA-YE-145133uaGate MB

Scope of Delivery

HardwareuaGate MB
SoftwareTool for configuration over integrated web interface
DocumentationQuick Startup Guide (printed documentation)

Les personnes intéressées par ce produit peuvent être intéressées par le produit suivant :

dataFEED EdgeGate

dataFEED EdgeGate : Connexion de vos PLCs Siemens et Modbus vers IoT Hubs

Passerelle pour connecter vos PLCs Siemens et Modbus vers un Cloud. Communication Bidirectionnel et hautement sécurisée vers la suite Microsoft Azure IoT

dataFEED edgeGate est la passerelle connectant les réseaux industriels vers des applications IT, fonctionnant “on premise” ou sur le Cloud.

La passerelle EdgeGate connecte vos PLCs with des applications OPC UA.  edgeGate connecte vos PLCs au Cloud, via le protocole MQTT. De plus la passerelle offre une intégration à de spécifique IoT Hubs Avec son standard OPC UA, la configuration est simple et la sécurité est optimale. La passerelle EdgeGate est facile et rapide à mettre en oeuvre avec de petites solutions et permets d’évoluer vers une charge plus importante.

Connection of IoT Hubs with Siemens and Modbus PLCs

  • Adjustable topic settings for MQTT payload
  • Perform analytics, monitoring, and create globally available dashboards in cloud solutions from different vendors, e.g. Amazon AWS, IBM Bluemix, Microsoft Azure
  • Integration of OPC UA and MQTT client applications running on-premise as well as in private and public clouds
  • Worldwide remote access to field data
  • Suited to new applications such as IoT or analytics
  • Use edgeGate for migration or retrofit upgrades
  • No PLC programming necessary
  • Symbol import from STEP 7 and TIA Portal projects
  • No software updates, operating system patches, or PC updates required

Integration with Microsoft Azure

  • Direct data access from Microsoft Azure to Siemens and Modbus PLCs
  • Bidirectional data exchange between cloud and shop floor by accessing OPC UA Servers on edgeGate or in OT network via integrated Microsoft OPC Proxy and Publisher components

Industry-proven Security

  • Physically separate interfaces and separate configuration rights for OT and IT networks preventing intrusions
  • Supporting security standards as SSL/TLS and X.509 certificates
  • OPC UA compliant data encryption and user authentification
HardwareProcessorAltera Cyclone V SoC with Dual-core ARM Cortex-A9
Connectors2 x IEEE 802.3 100BASE-TX/10BASE-T (independent interfaces)
Status LEDsPWR (power supply), RUN (running), ERR (error), SYS (configuration)
Dimensions (H x W x D)100 mm x 22.5 mm x 105 mm
Power Supply18 VDC … 32 VDC, SELV/PELV supply mandatory Typically 200 mA, maximum 1 A at switch-on
Operating Temperature, Horizontal DIN Rail Installation-40 °C .. 50 °C (0 mm minimum distance)
-40 °C .. 55 °C (22.5 mm minimum distance)
Operating Temperature, Vertical DIN Rail Installation-40 °C .. 35 °C (0 mm minimum distance)
-40 °C .. 40 °C (22.5 mm minimum distance)
Storage Temperature-40 °C .. 85 °C
Relative Humidity10 % … 90 %, non-condensing
WeightAbout 0.2 kg
MountingDIN Rail (35 mm)
HousingPhoenix Contact ME MAX
Protection ClassIP20
SoftwareIT Network / Cloud ConnectivityOPC UA (Server, 60,000 items in total), MQTT (Publisher, up to 1,000 topics)
Controller ConnectivityRFC1006, Modbus TCP
Maximum Number of Controllers5
Supported IoT HubsMicrosoft Azure connected factory, Microsoft Azure IoT Hub, IBM Watson IoT Hub, General Electric Predix, Amazon AWS, etc.
Supported ControllersSiemens S7-300, S7-400, S7-1200, S7-1500
Modbus TCP-compatible controllers (Schneider Electric, Wago, Beckhoff, Phoenix Contact, etc.)
Supported Engineering ToolsSIMATIC STEP 7, TIA Portal V13, V13 SP1, V14, V14 SP1
ConformityEmissionEC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55011, Group 1, Class A EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 55022, Class A EC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-4 FCC CFR45, Part 15 Section 15.107 and 15.109 (Class A), VCCI Class A Information Technology Equipment 2002
ImmunityEC Directive 2004/108/EC “Electromagnetic Compatibility”, EN 61000, Part 6-2
GAA-YY-145122edgeGate

Scope of Delivery

HardwareedgeGate
SoftwareTool for configuration over integrated web interface, dataFEED Exporter for easy symbol import from Siemens Project Files
DocumentationQuick Startup Guide (printed documentation)

Consultez nous pour des formations sur ce produit

epGatePN

epGatePN : Passerelle Ethernet IP -> PROFINET

Passerelle Ethernet IP vers PROFINET

Integration d’esclaves  PROFINET I/O via un mapping dans les systèmes de contrôles Ethernet IP

 

La passerelle epGatePN, élabore une passerelle entre un réseau Ethernet IP et jusqu’à 32 esclaves PROFINET. Alors qu’une des ports RJ45 se connecteau réseau Ethernet IP, l’autre port de la passerelle agit comme un controleur PROFINET. Il permet l’intégration de produits PROFINET à un réseau existant Ethernet IP. L’outil de configuration disponible, permet de définir la configuration PROFINET, d’utiliser les symboles et le “mapping” pour la/les PLCs Ethernet IP. Ainsi l’utilisateur est déchargé des taches suspectibles d’erreurs et défini individuellement l’accès aux données des 2 cotés de la passerelle.

Solutions similaires:
epGate DP: Integration de segments PROFIBUS DP dans un système Ethernet/IP
epGate PA: Integration de 4 segments PROFIBUS PA dans un système Ethernet/IP
epGate PB: Integration de 2 segments PROFIBUS PA  & 1 segment PROFIBUS DP dans un système Ethernet/IP

Simple Integration Through Add-On Instructions

  • Data access of PLC program to PROFINET Devices without requiring detailed PROFINET knowledge
  • Mapping between the two protocols generated by provided tools
  • Usage of Add-On Instructions (AOI), containing detailed PROFINET data type definitions
  • Transparent communication overcoming protocol differences

Time Saving Configuration Creation and Verification

  • Configuration tool for online access to PROFINET Devices via the network
  • Easy assignment of device properties
  • Early identification of discrepancies between offline configuration and real situation

Built-In Web Server For Monitoring And Interaction

  • Status information about both protocols
  • Monitoring of mapping as well as of exchanged data
  • Individual modification of FG-260 settings, including address information
  • Download and upload of all FG-260 configuration information using web server

Different Use Cases are addressed

  • Direct access from Ethernet/IP Scanner in the PLC to PROFINET field devices
  • Access to machines with internal PROFINET network by deploying I-Device capabilities
Hardware
ProcessorAltera Cyclone V SoC with Dual-core ARM Cortex-A9
Status LEDs (Gateway)PWR (power supply), RUN (running), ERR (error), CFG (configuration upload)
Status LEDs (EtherNet/IP)Net (network), Mod (module)
Status LEDs (PROFINET)SF (system fault), BF (bus fault)
Connectors2 x IEEE 802.3 100BASE-TX/10BASE-T (1 Ethernet port per protocol)
Dimensions (HxWxD)100 mm x 35 mm x 105 mm
Weightca 0.25 kg
Power Supply18 VDC … 32 VDC, SELV/PELV supply mandatory
Typically 200 mA, maximum 1 A at switch-on
Operating Temperature, Horizontal DIN Rail Installation-40 °C … 55 °C (0 mm minimum distance)
-40 °C … 65 °C (17.5 mm minimum distance)
Operating Temperature, Vertical DIN Rail Installation-40 °C … 40 °C (0 mm minimum distance)
-40 °C … 50 °C (17.5 mm minimum distance)
Storage Temperature-40 °C … 85 °C
Relative Humidity10 % … 90 %, non condensing
CoolingConvection, no fan
MountingDIN Rail (35 mm)
Protection ClassIP20
Software
ProtocolsEtherNet/IP Adapter (Up to 2 input and 2 output assemblies with up to 255 Bytes data each, minimum RPI: 8 ms)
PROFINET Controller (up to 8 devices at 1 ms cycle time)
Additional FunctionalityMapping application, web server
Supported Versions of Rockwell Automation PLC Programming SoftwareV16 – V21
Emission ConformityEC Directive 2004/108/EG “Electromagnetic Compatibility“, EN 55011, Group 1, Class A
EC Directive 2004/108/EG “Electromagnetic Compatibility“, EN 55022, Class A
EC Directive 2004/108/EG “Electromagnetic Compatibility“, EN 61000, Part 6-4
FCC CFR45, Part 15 Section 15.107 and 15.109 (Class A),
VCCI Class A Information Technology Equipment 2002
Immunity ConformityEC Directive 2004/108/EG “Electromagnetic Compatibility“, EN 61000, Part 6-2
CertificationsCE
EN/IEC 61010-1 and CB
EN/IEC 61010-2-201 and CB
UL 61010-1 and UL 61010-2-201
GCL-CA-010260FG-260

Scope of Delivery

HardwarePasserelle epGatePN
SoftwareEDS File, Outils de configuration et outils de recherche sur CD
DocumentationQuick Startup Guide documentation, User Guide sur CD-ROM

People interested in this product, might be interested in :

THLink Profinet

echocollect -e

La passerelle echocollect -e

La passerelle Echocollect est une passerelle dédiée à l’intégration des données “Process Data” vers des systèmes de hauts niveaux ou de solutions IoT.

La passerelle echocollect -e est une passerelle multi protocoles fournissant des solutions de managment “Process Data”. Elle offre des connexions “temps réel” entre PLC et bases de données,  OPC UA et OPC Classic connectivité. Ses fonctionnalités inclues à la fois le log de données locales et une intégration directe de données d’applications Cloud IoT via MQTT

 

 

Vous ne connaissez pas l’ echocollect ???

Présentation Echocollect  ( PDF )

Integration of Existing Systems in New Quality Assurance Systems

  • Independent real-time collection of manufacturing, process or quality data directly from programmable logic controllers (PLC) and delivery to higher-level management systems, such as ERP or MES system
  • Recipe manager functionality for writing data blocks to PLCs
  • Direct connectivity via SQL database protocols, platform independent OPC UA technology or MQTT Publisher functionality
  • Support of more than 50 PLC types addressable via Ethernet

Excellent Data and Network Security

  • Buffering of arriving data and addition of time stamps in case of broken connections, automatic forwarding once connection has been reestablished
  • Option for parallel data logging on SD card for traceability reasons
  • Physical network separation between production systems and commercial IT networks
  • State-of-the-art OPC UA security: Optional encryption of transmitted data and authentication via certificates

Lowered IT Maintenance Costs and Investment Protection

  • echocollect as standard component, addition of extra functionality without modifying existing systems
  • No need for additional PC requiring software updates and administration
  • Working for years once configured – untouched, without updates and with zero maintenance costs
  • Plug-and-go replacement, if necessary, using configuration stored on SD card
  • Very easy configuration by straightforward project import without requiring PLC modifications and programming skills

Easy Live Data Visualization

  • Native web technology for easy and cost-efficient visualization of process, manufacturing and quality data using standard web browser without any plug-ins
  • No need for OPC Server or complex SCADA system
  • Scalable, resolution-independent vector graphics for consistent display of data on wide variety of network enabled devices like desktop PCs, laptops, smart phones, tablet PCs or industrial control panels
Ethernet Addressable ControllersSiemens SIMATIC S7 and S5, controllers with Modbus TCP (Wago, Beckhoff, Phoenix Contact, Schneider Electric, etc.), Mitsubishi (Melsec-Q), etc.
Ethernet ProtocolsTCP/IP, RFC1006 (ISO on TCP), ISO (H1), S5, S7, TCP/IP with PLC header, Modbus TCP, Melsec-Q, raw data
Ethernet Interfaces2 x independent interfaces TP (RJ45), 10/100 MBit/s
Embedded OPC UA ServerSymbolic Mapping; Browsing, Read, Write, Subscribe; Self-Discovery Service; possible reconfiguration without device restart; possible multiple Client connections, optional read-only PLC connection; OPC UA Security with password or certificates
Embedded MQTT PublisherEstablishment of MQTT Broker connection, optional user authentication and data encryption, easy topic generation from existing symbols, maximum of 1,000 topics, adjustable publishing interval
Supported DatabasesMySQL, Oracle, DB2, MS-SQL
Other ProtocolsTelnet, SMTP (email notification), OPCpipe (OPC Tunnel)
Supported Engineering Tools for Symbol ImportSIMATIC STEP 7, TIA Portal
LimitationMaximum of 5 PLC connections, 10,000 items in total
Data mapping PLC – database must be structured in 400 tables and 200 items per table
Visualizationatvise webMI visualization, functional level ‘Advanced’ (fully event-driven data exchange) Limited to up to 50 visualized items per echocollect (optional upgrade possible), maximum of 5 simultaneously accessing browsers
Configuration SoftwareSofting NetCon for device configuration, atvise builder for SCADA project editing, dataFEED Exporter for symbol import
Power Supply24 VDC, ca. 0,3 A
Ambient ConditionsOperating temperature: 0 °C … 55 °C, storage temperature: -20 °C … 70 °C
Dimensions (HxWxL)131mm x 47mm x 111mm
Weightca. 0,4 kg
Mounting35 mm DIN Rail
Protection ClassIP20
CertificationsCE
GAL-YY-143101echocollect e (connectors: 2 x Ethernet, 1 x TTY)
LRA-YY-143001Upgrade echocollect: License for database access to Oracle, DB2 and MSSQL (default: MySQL only)
LRA-YY-143002Upgrade echocollect: License enabling data logging on SD Card (default: no data logging)
LRA-YY-143004Upgrade echocollect: License supporting unlimited number of visualization items (default: maximum of 50 visualization items)
LRA-YY-143005Upgrade echocollect: License embedded OPC UA Server (default: no embedded OPC UA Server)
LRA-YY-143007Upgrade echocollect: License MQTT Publisher functionality (default: no MQTT support)
LRA-YY-143115Upgrade echocollect: License enabling maximum of 15 PLC connections (default: maximum of 5 PLC connections)

Additional Products and Services

700-5596-04AC Adapter, 24 VDC, Euro, UK, or USA
LRL-DY-131701OPCpipe client
MEA-YY-144002CD atvise elements, 4,000 high-quality bitmaps and vector graphics in SVG format
GPL-CS-191000echolink sS7-compact
110-1000-01Industrial Ethernet – Troubleshooting in Automation, 3 days

Scope of Delivery

HardwareMulti-protocol gateway echocollect e, SD card, connector for power supply*
SoftwareNet configuration software on CD-ROM, also downloadable from Softing website
DocumentationQuick Start leaflet, context-based online help, CD-ROM with product handbook and configuration tutorials, also downloadable from Softing website

Connector Power Pack 24 V DC

Country-specific connector power packs are available. Note: A connector power pack is not included in the delivery of the echocollect. If necessary please order it separately.

Technical Details

100 – 240 V AC, 47 – 63 Hz, sec. 24 V, 1,25A

Order Number

Version EURO, UK, USA
700-5596-04

Which cloud platforms are supported?

We support with all Softing gateways (echocollect, uaGate, edgeGate) the Microsoft Azure Cloud, Amazon AWS Cloud, IBM Bluemix Cloud and other cloud providers, which are using MQTT for telemetry data.

What is the size of the Store & Forward queue on the echocollect?

The S&F queue for MQTT is unlimited (except the size of the sd-card). The echo buffers in the ram, and after it collects a bunch of messages, they were copied to the sd-card. To use the S&F feature, QoS 1 or QoS 2 must be used.

Les personnes intéressées par ce produit, peuvent être intéressées par :