pnGate PB
Connection
PN Gate PB: Direct integration of PROFIBUS DP and PA segments into a PROFINET control system
In stock
SKU: GCA-AN-024608 Categories: PROCESS AUTOMATION, PROFIBUS Gateways, PROFINET
Description
PROFINET to PROFIBUS DP/PA Gateways ( pnGate PB )
Direct integration of PROFIBUS DP and PA segments into a PROFINET control system
- Re-use “power confectioners” in a network update project
- No intermediate PROFIBUS DP segments.
- Prepare for standard integration and Asset Management tools.
Key Component for Transition to State-of-the-Art Technology
- Simple replacement of installed PROFIBUS DP/PA segment coupler
- Re-use of existing PROFIBUS segments without requiring modification
- Support of PROFINET redundancy for increased reliability
Direct Connectivity to PROFIBUS Segments
- Single access point to PROFIBUS DP and PROFIBUS PA segments from PROFINET networks
- Acting as PROFINET Device, PROFIBUS PA and PROFIBUS DP Master
- Support of one PROFIBUS DP segment and up to two PROFIBUS PA segments
Configuration, Parameterization and Plant Asset Management Using Standard Industry Tools
- Supports major PROFINET engineering tools such as TIA Portal, Step7 and PC WORXS
- Included CommDTM allowing use in FDT/DTM frame applications
- EDD-based device parametrization using Siemens Simatic PDM
Technical Details | ||
---|---|---|
Hardware | Processor Status LEDs (Gateway)Status LEDs (Fieldbus) | Altera Cyclone V SoC with dual-core ARM Cortex-A9 PWR (power supply), RUN (operation), ERR (error), CFG (configuration and update) SF (system fault), BF (bus fault) |
Interfaces and Connectors | Ethernet PROFIBUS PA PROFIBUS DP-V0 / V1 | 2 * IEEE 802.3 100BASE-TX / 10BASE-T, embedded PROFINET switch for daisy chain topology Connectors: RJ45 Protocol: PROFINET RT / IRT, Support of PROFINET redundancy protocols RESTful API interface for device configuration 2 * PROFIBUS PA (MBP) segments, Bus-powered Medium Attachment Unit (MAU): Fieldbus voltage range: 9 VDC … 32 VDC, current consumption 10 mA, Connectors: 3-position screw connection, galvanically isolated 1 Segment with RS485 Physical Layer, Connector: 9-pin Sub-D socket |
Physical Properties | Dimensions (H x W x D) Weight Power SupplyOperating / Storage Temperature Relative Humidity Cooling Coating Mounting Protection Class | 100 mm x 35 mm x 115 mm Approx. 0.25 kg 18 VDC … 32 VDC; SELV/PELV power supply mandatory Typical input current: 200 mA, maximum input current: 1 A (allowing for in-rush current at switch-on) No power supply to PROFIBUS PA segments through pnGate PB -40 °C … +70 °C / -40 °C … +85 °C (see detailed mounting description in user manual) 10 % … 95 %, non-condensing Convection, no fan Conformal coating based on ANSI / ISA-S71.04 G3 DIN rail 35 mm IP20 |
Scope of Delivery | |
---|---|
Hardware | pnGate PB Gateway |
Software | GSDtoGSDML Converter, FDT CommDTM, PACTware, Drivers and Tools |
Documentation | On CD-ROM |
Order Numbers | |
---|---|
GCA-AN-024608 | pnGate PB, PROFINET to PROFIBUS Gateway. Supports up to 2 PROFIBUS PA segments (up to 32 PA devices, MBP physical layer) and 1 PROFIBUS DP segment (RS485). |
Additional Products and Services | |
---|---|
GCA-AL-024602 | pnGate PA, PROFINET to PROFIBUS-PA Gateway. Supports up to 2 PROFIBUS PA segments (up to 32 PROFIBUS PA devices). |
GCA-AL-024604 | pnGate PA, PROFINET to PROFIBUS-PA Gateway. Supports up to 4 PROFIBUS PA segments (up to 64 PROFIBUS PA devices). |
GCA-AL-024605 | pnGate PA (for STAHL carrier), PROFINET to PROFIBUS-PA Gateway. Supports up to 4 PROFIBUS PA segments (up to 64 PROFIBUS PA devices). For reversed mounting position on STAHL backplane |
GCA-EL-024802 | mbGate PA, Modbus/TCP to PROFIBUS-PA Gateway. Supports up to 2 PROFIBUS PA segments (up to 32 PROFIBUS PA devices). |
GCA-EL-024804 | mbGate PA, Modbus/TCP to PROFIBUS-PA Gateway. Supports up to 4 PROFIBUS PA segments (up to 64 PROFIBUS PA devices). |
pnGate : Profinet to Profibus DP/PA
A savoir
Sous Firmware v 1.30 Login : administrator Password : FGadmin!1